HIMA F-7133 4-channel power distribution module
Channel parameters: With 4 channels, it can handle the power distribution needs of four channels at the same time, each channel has a rated current of 2.5A, and the total load capacity can reach 10A.
Input and output voltage: Input voltage ranges from 12V DC to 24V DC, and output voltage is 24V DC.
Fuse specification: Equipped with 4 micro fuses, the maximum current is 4A slow melt, providing overcurrent protection for the circuit.
Relay parameters: The switching time is about 100ms, and the load capacity of the relay contact is 30V/4A (continuous load).
Residual voltage and current: in the case of fuse trip, the residual voltage is 0V and the residual current is 0mA; In the absence of power supply, the maximum residual voltage is 3V and the residual current is less than 1mA.
Electrical connection: Contact pins (1, 2, 3, 4 and L -) on the front are used to connect L + (EL +) and L – to supply power to the IO module and sensor contacts; There are contacts on the back (D6, D10, D14, D18), which serve as rear terminals to provide 24V power to each IO slot.
Status indication: Each fuse is associated with an LED, monitored by evaluation logic, informing the relevant LED of circuit status in real time. The LED lights up when the fuse is normal, blinks when the fuse is faulty or missing, lights up when the power supply voltage is present, and turns off when the power supply voltage is faulty.
Operating temperature: The operating temperature range is -20 ℃ to + 55℃.
Certification: Passed CE, UL and other certifications.